Lighting switch controller
PCL0808
Performance
● Lighting controllers
● AC 220V operating voltage
● 8 dry contact inputs
● 8 x 20A relay outputs (with manual switch)
● DC24V, DC12V sensor power supply
● 1 sensor access
● 1 RS485 panel input
● 1 BACnet MS/TP port
Use
The main function is the input of the remote lighting switch, which controls the switch of the lighting circuit. It can be operated stand-alone or networked. The communication interface is RS485, the communication protocol is BACnet MS/TP, the baud rate is 9600~76.8K bps, and the default is 38.4K bps.
Built-in direct controller application
The lighting controller uses an independent Direct Digital Control (DDC) that provides monitoring of the lighting circuit. The controller has the following functions:
●Switch control
●Schedule control
●Mode control
List of input and output points
enter | output | model | ||
analog point | digital point | analog point | digital point | |
1 | 8 | 0 | 8 | PCL0808 |
Mechanical Design
Housing PCL0808 controller is a compact unit according to DIN 43 880 Gr. 1
Installation methods PCL0808 controller has the following installation methods:
Installed in standard electrical control box according to DIN 43 880 standard rail
●Wall mounted in protective enclosure
●Installation from the front with standard mounting elements (screws)
Terminals Plug-in terminals are screwed on.
Technical data
power supply | Operating Voltage | AC 220V ±20% |
Frequency | 50Hz | |
CPU | Cortext-M3 | |
RAM | 128K | |
FLASH | 512K | |
Power consumption | PCL0808 | 20VA |
Communication Interface | RS485 interface | BACnet MS/TP |
transport environment | temperature | -25~70℃ |
humidity | <95% RH | |
working environment | temperature | 0~50℃ |
humidity | <95% RH | |
IP rating | IP20 EN60529 | |
Product Standards | Standard for automatic control of air-con ditioning related applications | EN 60730 |
Terminals | Plug-in screw-on terminals, suitable for: Smaller diameter 1.5mm | |
Large diameter 2x1.5mm² | ||
Controller size | 180mm X 90mm X67mm (L X W X H) | |
address definition | Device Instance and MAC address are defined by software |
Installation dimension drawing (unit: mm):