Controller

Controller

  • Category:Controllers
  • Browse number:
  • QR code:
  • Release time:2022-03-09 10:12:19
  • Product description


Controller

PCC2010

Performance

• Universal controller 

• AC/DC 24V operating voltage 

• 4 analog input points (AI) support NTC10K/0... 10 V/4-20mA(12bit)

• 16 digital input points (DI)

• 2 analog output points (AO) DC 0... 10 V signal

• 8 relay outputs (D0) 3A@250VAC

• 2 RS485 communication ports


Use

The controller is mainly suitable for comfort control of HVAC systems and refrigeration systems. It can be mounted separately in the control panel or on pipes, walls and machine rooms. It can be operated stand-alone or networked. Communication interface 1 is RS485, communication protocol is BACnet MS/TP, the default baud rate is 38.4K bps, communication interface 2 is RS485, R-BUS private protocol.


Built-in direct controller application

The controller uses independent direct digital control (DDC) to provide proper HVAC control and comprehensive information about system operation. The controller receives information from sensors in the field and controls the device directly. The controller has the following functions:

●Adaptive control, a closed-loop control algorithm with self-learning and adjustment. More efficient, adaptable, more responsive, and more stable control than traditional PID algorithms. In particular, it has advantages in response time and maintenance status. It also reduces errors, oscillation and drive wear

●Closed-loop proportional and integral and derivative (PID) control

● Logical sequence control

● Alarm monitoring and reporting


List of input and output points

enteroutputmodel
analog point digital pointanalog pointdigital point
41628PCC2010


Technical data

 power supply

 power supply

 AC 24V ±20%


 power supply

 50Hz

 FLASH


 512K

 power supply

 PCC2010

 6VA

 Communication I nterface

 RS485 interface

 BACnet MS/TP

 Modbus RTU

 transport environment

 temperature

 -25~70℃


 humidity

 <95% RH

 working environment

 temperature

 0~50℃


 humidity

 <95% RH

 IP rating


 IP20 EN60529

 Terminals

 Plug-in screw-on terminal blocks, suitable for: diameter smaller than 1.5mm diameter


                                                                             Large diameter 2x1.5mm²


 Controller size

 178mm X 132mm X 57mm (L X W X H)

 address definition

 Device Instance and MAC address are defined by software


Installation dimension drawing (unit: mm): 