PCC2010
Performance
• Universal controller
• AC/DC 24V operating voltage
• 4 analog input points (AI) support NTC10K/0... 10 V/4-20mA(12bit)
• 16 digital input points (DI)
• 2 analog output points (AO) DC 0... 10 V signal
• 8 relay outputs (D0) 3A@220VAC
• 2 RS485 communication ports
Use
The controller is mainly suitable for comfort control of HVAC systems and refrigeration systems. It can be mounted separately in the control panel or on pipes, walls and machine rooms. It can be operated stand-alone or networked. Communication interface 1 is RS485, communication protocol is BACnet MS/TP, the default baud rate is 38.4K bps, communication interface 2 is RS485, R-BUS private protocol.
Built-in direct controller application
The controller uses independent direct digital control (DDC) to provide proper HVAC control and comprehensive information about system operation. The controller receives information from sensors in the field and controls the device directly. The controller has the following functions:
●Adaptive control, a closed-loop control algorithm with self-learning and adjustment. More efficient, adaptable, more responsive, and more stable control than traditional PID algorithms. In particular, it has advantages in response time and maintenance status. It also reduces errors, oscillation and drive wear
●Closed-loop proportional and integral and derivative (PID) control
● Logical sequence control
● Alarm monitoring and reporting
List of input and output points
enter | output | model | ||
analog point | digital point | analog point | digital point | |
4 | 16 | 2 | 8 | PCC2010 |
Technical data
power supply | power supply | AC 24V ±20% |
power supply | 50Hz | |
FLASH | 512K | |
power supply | PCC2010 | 6VA |
Communication I nterface | RS485 interface | BACnet MS/TP Modbus RTU |
transport environment | temperature | -25~70℃ |
humidity | <95% RH | |
working environment | temperature | 0~50℃ |
humidity | <95% RH | |
IP rating | IP20 EN60529 | |
Terminals | Plug-in screw-on terminal blocks, suitable for: diameter smaller than 1.5mm diameter | |
Large diameter 2x1.5mm² | ||
Controller size | 178mm X 132mm X 57mm (L X W X H) | |
address definition | Device Instance and MAC address are defined by software |