Network controller
PCC2412E
Performance
●Network type universal controller
●2 RJ45 interfaces and 2 RS485 interfaces
●AC/DC 24V working voltage
●8 universal input points for NTC10K, 0... 10 V, 4... 20mA, dry contact
●16 digital input points (dry contacts)
●6 analog output points output DC 0... 10 V signals
●6 relay outputs
●Supports Modbus TCP, BACnet IP, MQTT protocols
●1 RS485 port can come with 5 R-BUS expansion modules
●1 RS485 port Modbus RTU master station communication
●Supports connecting touch screens
Use
The network universal controller is mainly suitable for comfort control of HVAC systems and refrigeration systems. It can be installed separately in the control panel or on pipelines, walls, and in the computer room. It can run independently or online.
Built-in direct controller application
The controller adopts independent direct digital control (DDC), which can provide monitoring of lighting, water pump, air supply and exhaust fan and other equipment. Controls and comprehensive information about system operation. The controller has the following functions:
●Closed loop proportional, integral, and derivative (PID) control
●Logical sequence control
●Alarm monitoring and reporting
●Schedule control
List of input and output points
Enter | Output | Model | ||
common point | digital point | A point | digital point | |
8 | 16 | 6 | 6 | PCC2412E |
function
PCC2412E is a network-based controller, and graphical programming software provides rich programming modules that can be used for HVAC control and independent control of small projects.
PCC2412E supports three protocols: BACnet IP, Modbus TCP, and MQTT. In large-scale projects, multiple PCC2412E can be connected to form a network.
The built-in control points of PCC2412E can control building equipment such as chillers, air conditioners, and fresh air fans, directly forming the building's energy management system through the building's basic network, saving the tedious communication bus layout costs and providing convenience for future maintenance of the building.
Technical data
Technical data | Operating Voltage | AC 24V ±20% |
frequency | 50Hz | |
CPU | Cotex M4 | |
PCC2412E | 10VA | |
Communication Interface | RJ45 interface (2) | BACnet IP Modbus TCP MQTT |
RS485 interface (2) | Modbus RTU R-BUS | |
Transport environment | temperature | -25~70℃ |
humidity | <95% RH | |
Humidity | temperature | 0~50℃ |
humidity | <95% RH | |
IP rating | IP20 EN60529 | |
Product Standards | Standard for automatic control of air-conditioning related applications | EN 60730 |
Terminals | Plug-in screw-on terminals, suitable for: Smaller diameter 1.5mm | |
Large diameter 2x1.5mm² | ||
Controller size | 213mm X 131mm X60mm (L X W X H) | |
Address definition | Software-defined Device Instance and MAC address |