PCV-10D/DF PCV-15D/DF PCV-20D/DF PCV-30D/DF | On-off Air Valve actuator 10Nm/15Nm/20Nm/30Nm Two-point control and Three-point control |
Used to drive the HVAC and all kinds of mechanical ventilation system air valve Output Torque:10Nm,15Nm, 20Nm,30Nm Supply Voltage:AC/DC24V Control Mode:Switch control/ Two-point control/ Three-point control DF type with two sets of auxiliary switch |
Technical parameter | |||||
PCV-10D/DF | PCV-10D/DF | PCV-20D/DF | PCV-30D/DF | ||
Electrical parameter | rated voltage | AC24V 50/60Hz DC24V | |||
Rated voltage range | AC/DC 19.2...28.8V | ||||
Power consumption | Running state 4.5W,standby state 0.5W | ||||
Wire Specification | 0.5 mm² | ||||
Terminal Specification | Max 2mm² | ||||
Functional parameter | Torque | 10Nm | 15Nm | 20Nm | 30Nm |
Fit Air Valve area | 1.5m² | 3m² | 4m² | 5m² | |
Direction of rotation | Manual adjustment | ||||
Manual operation | Have | ||||
Angle of rotation | Max 95° | ||||
Running time | 30S~45S(95°) | 30S~45S(95°) | 120S~160S(95°) | 160S~200S(95°) | |
Noise level | 45dB | ||||
Position Indication | Mechanical indication | ||||
Working Environment | Electrical Grade | Ⅱ(Double insulation) | |||
Protection level | IP54 | ||||
Working Environment | -20…+50℃ | ||||
Storage ambient | -30…+80℃ | ||||
Maximum ambient | 95%RH,No Dew | ||||
Size/weight | Dimensions | See size chart for details | |||
Length of air valve shaft | >50mm | ||||
Air Valve shaft | 10...20mm Circular Shaft 10X10...16X16 Square axis | ||||
Weight | 1.3Kg |
Wiring Diagram
Two-point connection Three-point connection
Resistive load 3A,220V
Perceptual load 1.5A,220V
Dimensional drawing(mm)
Change the rotation direction of the actuator
Factory set to 1,2 terminal power clockwise direction.
Power supply | 1,2 Terminal | 1,3 Terminal |
Actuator direction of rotation | Clockwise | Counterclockwise |
The actuator direction can be adjusted by changing the
state of the sliding switch S1.
-DF type auxiliary switch adjustment
Factory setting
Switch a | Terminal 01,02 | Terminal 01,03 |
0-10° | Open circuit | Short circuit |
10-90° | Short circuit | Open circuit |
Switch b | Terminal 04,05 | Terminal 04,06 |
0-80° | Open circuit | Short circuit |
80-90° | Short circuit | Open circuit |
Set Auxiliary switch a: Turn The actuator clockwise to the angle to be set, loosen the screw of knob A, turn Knob a clockwise to just press down the micro switch, maintain this position, and re-tighten the screw.
Set Auxiliary switch b:Turn the actuator clockwise to the desired angle, loosen the screw on Knob B, Turn Knob B clockwise to release the microswitch, hold this position, and re-tighten the screw.
Points to note
1.This valve actuator shall not be used outside the specified application, especially not on aircraft.
2.Non-professional installation personnel do not open the actuator Shell, strictly prohibited live wiring.
3.This Air Valve actuator contains electronic component and shall not be treated as ordinary household waste and shall be treated in accordance with local laws and regulations.