Touch the air conditioner thermostat
PCC-FCU-4G
Product Overview
PCC-FCU-4G Air Conditioner Thermostat is a newly developed LCD large-screen touch LCD display for market demand. The panel design is simple and clear to operate, and the keys are fully functional. Controllable equipment: three-speed fan, three-wire and two-wire electric valves, solenoid valves, etc.
Technical parameters
●Operating voltage:AC220~240V,50/60Hz
●Temperature control accuracy:±1℃
●Self-consumed power:﹤0.5W
●Load current:﹤3.15A
●Set the temperature range:10℃-40℃
●Temperature sensor:NTC
●Panel dimensions:86*86*14mm(H*W*D)
Instructions
(1)Feature description
1、On/Off: Press the "" key.
2、Temperature setting: By increasing "▲" and decreasing "▼" adjustment, the factory default temperature is 26°C.
3、Mode settings: Press "" to select " "Heating;" "Refrigeration;" " ventilation. The default mode for power-on is "" ventilation.
4、Wind speed setting: The factory default fan mode is " "(Low). Press the "" button to select the wind speed : (low), (medium), (high), (automatic), if you select (automatic), the fan will automatically adjust according to the room temperature and the set temperature.
(2) Time timing setting
1、 Time setting: press the "" button for more than 7 seconds until the "hh" flashing of "hh:mm" appears, press "▲", "▼" to adjust the hour; After the hour adjustment is accurate, press the "" button until the "mm" of "hh:mm" flashes, press "▲", "▼" to adjust the minute, and it will be automatically confirmed after 7 seconds after the adjustment is completed. Then press the "" button, in the day setting area until "1, 2, 3, 4, 5, 6, 7" flashes, press "▲", "▼" to adjust the day, 1 means Monday, 2 means Tuesday, and so on.
2、Timed power-on setting: Press the "" button for more than 7 seconds, after setting the time, press the "" button again until the "HH" of "" and "HH:mm" flashes, press "▲", "▼" to adjust the hour; After the hour adjustment is accurate, press the "" button until the "mm" of "hh:mm" flashes, press the "▲", "▼" button to adjust the minute, and press the "" button to confirm after the adjustment, at this time, the "" will no longer flash, and the timing boot setting is completed. The operation method of canceling the timer boot setting is the same as the boot method, press the "" button to the timer boot state, and then press the "" button, at this time, the "" flashes and the timed boot has been canceled.
3、Timer shutdown setting: After setting the timer to turn on the computer, press the "" button until the "hh" of "" and "hh:mm" flash, and press "▲" and "▼" to adjust the hours; After the hour adjustment is accurate, press the "" button until the "mm" of "hh:mm" flashes, press "▲", "▼" to adjust the minute, press the "" button to confirm after the adjustment, at this time the "" will no longer flash, and the timer shutdown setting is completed. The operation method of canceling the timer shutdown setting is the same as the shutdown method, press the "" key to the timer shutdown state, and then press the "" button, at this time, the "" flashes and the timer shutdown has been canceled. The third and fourth periods are turned on settings: the same as the first and second periods, and the icon "" turns off and on (out of the house, into the house).
4、Seven-day cycle setting: After the timer is set to power on and off, press the "" button again, and the loop will be displayed. Press "▲", "▼" to adjust 12345 means that the timer switch is valid from Monday to Friday, seven days a week, 123456 means that the timer switch from Monday to Saturday is valid for seven days a week, and 1234567 means that all seven are valid.
(3)Advanced settings (recommended by professionals)
In the shutdown state, press "" first, and then press "" to enter the advanced settings; For details, please refer to the following table (press "" in the next step)
Serial number | Display symbols | Set up the project | Parametric device function | Factory default |
1 | dIF | Indoor temperature control backdrop | 0.5-2℃ | 1℃ |
2 | SH1 | Set the maximum upper limit of the refrigeration temperature | 10-40℃ | 40℃ |
3 | SL1 | Set the minimum refrigeration temperature limit | 10-40℃ | 10℃ |
4 | SH2 | Set the maximum upper limit of heating temperature | 10-40℃ | 40℃ |
5 | SL2 | Set the minimum lower limit of heating temperature | 10-40℃ | 10℃ |
6 | AdJ | Measurement temperature correction | -5-5℃ | 0 °C (0.5 °C corrected resolution) |
7 | FAN | Fan temperature control mode | 0: The fan is controlled 1: The fan is not controlled | 0: The fan is controlled |
8 | FrE | Antifreeze function | 00: The antifreeze function is turned off 01: The antifreeze function is turned on | 00: The antifreeze function is turned off |
9 | LOC | Keylocks | 0: No lock 1: Half lock 2: Full lock (Temporarily unlock and press and hold the fan button 7 seconds time) | 0: No lock |
10 | Pon | Power-on and power-on memory | 00: No memory when powered on 01: Power-on memory | 00: No memory when powered on |
11 | FAC | Factory settings | 08: It's just a show, no other meaning 00: Factory reset | 08 |
Note: Description of the remark: The initial indoor control temperature value is set to 22°C, the indoor control temperature rearity (dIF) is set to 1, when the temperature drops to 21°C, the relay stops output, and when the temperature rises to 22°C, the relay re-outputs and cools.
Installation Instructions
1. Disconnect the power supply before starting the installation to prevent electric shock or damage to the equipment.
2. According to the specified rated current, it is forbidden to overload.
3. The installation line must use a single strand hard wire of 1.5-2.5 mm².