玉溪Carbon dioxide sensor

玉溪Carbon dioxide sensor

  • Category:玉溪Sensor
  • Browse number:
  • QR code:
  • Release time:2022-02-26 15:45:33
  • Product description

Carbon Dioxide Sensor

PCT-CO2-R

二氧化碳传感器

Product information

The PCT-CO2 indoor CO2 sensor is suited for all types of building controllers and can offer accurate and reliable measurement results. The sensor makes use of an imported CO2 detecting module and detects CO2 in the air using the non-dispersive infrared (NDIR) principle. It has good selectivity, does not require oxygen, and has a long life. It has a steady and reliable power supply, as well as multiple output signals with outstanding stability and anti-interference.


Technical criterion

A. High sensitivity, high resolution, and low power consumption

B. Digital signal noise reduction with high stability

C. Simple to operate, with a jumper to select linear output. 0-10V or 4-20mA

D.  BACnet MS/TP or Modbus RTU communication output

E. Quick response time, temperature correction, high stability, and extended service life

 

Technical Specifications

Product number

PCT-CO2

detect gas

carbon dioxide

Operating Voltage

24VDC/AC±10%

Average current

< 150mA

output signal

1 channels CO2 signal: 0~10V or 4~20mA/DC

BACnet MS/TP or Modbus RTU

Preheat time

30min

Operating temperature

0~95%RH (no condensation)

Dimensions

86×86×27mm(L×W×H)

weight

100 g

life

>5 years


Metrics and Precision

Name

Range

Precision

Remark

carbon dioxide

0~2000ppm

±(50ppm+

5% reading value)

Temperature compensation


Settings and Parameters

Jumpers are used to set the analog signal output type, please set according to the following table, BACnet parameters are shown in the following table:

Jumper wire

Account for

Output

Modbus Output address

BACnet address

J1

CO2

V:0-10V  C:4-20m

30001

AI0


Wiring diagram

Precautions & Installation

A. The sensor should be put in a position that is reasonably stationary.

B. Connect the sensor to the controller once all other electronics and tests have been completed.

C. Check to see if the power supply voltage is within the rated range.

D. To avoid the control wires passing through regions with high magnetism and noise, use screened cables to connect; do not hang heavy things on the wires.

E. To minimize saturated condensation, the sensor should not be in direct contact with water and should not be exposed. To avoid any harm, non-professionals are not permitted to disassemble electronic components and sensors.