  • Product description

Carbon Monoxide Sensor

PCT-CO-R

一氧化碳传感器

Product description

PCT-CO indoor CO sensor can provide accurate and reliable measurement data, suitable for all kinds of building controllers. The sensor utilizes an imported CO sensing module and uses the principle of non-dispersive infrared (NDIR) to detect CO present in the air. It has good selectivity, no oxygen dependence, and long life. Built-in temperature compensation, equipped with reliable and stable power supply and various output signals with excellent stability and anti-interference.


Technical parameter

A. High sensitivity, high resolution, low power consumption

B. High stability digital signal noise suppression

C. Easy to use, jumper to choose linear output 0-10V or 4-20mA

D. BACnet MS/TP or Modbus RTU communication output

E. Fast response time, temperature compensation, excellent stability, long service life


Technical Specifications

Product number

PCT-CO

detect gas

carbon monoxide

Operating Voltage

24VDC/AC±10%

Average current

< 150mA

output signal

1 channels CO2 signal: 0~10V or 4~20mA/DC

BACnet MS/TP or Modbus RTU

output signal

30min

Operating temperature

0~50℃

Working humidity

0~95%RH (no condensation)

Dimensions

86×86×27mm(L×W×H)

weight

100 g

life

>5 years


Metrics and Precision

Name

Range

Precision

Remark

carbon monoxide

0~200ppm

±(10ppm+

5% reading value)

Temperature compensation


Settings and Parameters

Jumpers are used to set the analog signal output type, please set according to the following table, BACnet parameters are shown in the following table:

Jumper

Illustrate

Output

Modbus output address

BACnet address

J1

CO

V:0-10V  C:4-20mA

30001

AI0


Wiring diagram

Installation and Precautions

A. The sensor should be installed in a relatively stationary position.

B. After all other electronics and tests are complete, connect the sensor to the controller.

C. Ensure that the power supply voltage is within the allowable rated range.

D. It is recommended to use the screened wires to connect to avoid the control wires going through places with large magnetism and noise; do not hang heavy objects on the wires.

E. The sensor should not be in direct contact with water and should not be exposed to avoid saturation condensation. Non-professionals are not allowed to dismantle electronic components and sensors to avoid possible damage.

 

Order information

PCT-CO-R       Indoor carbon monoxide sensor (BACnet MS/TP or Modbus RTU)